|
Info Library
Recommended Reading:
Reference Info:
Conversion Tables:
Online Safety Training:
Resource Center:
Free Info:
Email For:
Need Assistance?
|
|
|

Interested in
having timely and informative safety-related information sent directly
to your e-mail box? LSS publishes our no-charge Saf-T-News every other
week. To begin receiving your copy, click here.
Use, Placement, Maintenance and Testing of Portable Fire Extinguishers

Document Number: 135
Introduction
Almost all fires are small in their early stage and can be put out quickly
if the proper fire
extinguisher is available, and the person discovering the fire has
been trained to use the fire extinguisher at hand. The requirements for
portable fire extinguishers in general industry are governed by OSHA regulation
29
CFR 1910.157.
To be effective, portable fire extinguishers must be:
- Approved by a recognized testing laboratory (Extinguishers manufactured
in the U.S. are generally approved by FM
Global (FM) and listed by Underwriters'
Laboratories, Inc. (UL));
- Of the proper type for the class of fire expected;
- Located where they are readily accessible for immediate use and in
sufficient quantity and size to deal with the expected fire;
- Inspected and maintained on a regular basis so that they are kept
in good operating condition; and
- Operated by trained personnel who can use them effectively.
Classification
Fire extinguishers are classified by the type of fire that they will
extinguish.
 |
A Class A fire extinguisher is used for ordinary combustibles,
such as wood, paper, some plastics and textiles. This class of fire
requires the heat-absorbing effects of water or the coating effects
of certain dry chemicals. Extinguishers that are suitable for Class
A fires should be identified by a triangle containing the letter
"A." If in color, the triangle should be green. For Class
A fire extinguisher options, please see LSS#
8774, 5467, 7376, 1123, 3820. |
 |
A Class B fire extinguisher is used for flammable liquid
and gas fires such as oil, gasoline, etc. These fire extinguishers
deprive the fire of oxygen and interrupt the fire chain by inhibiting
the release of combustible vapors. Extinguishers that are suitable
for Class B fires should be identified by a square containing
the letter "B." If in color, the square should be red. For
Class B fire extinguisher options, please see LSS#
8774, 5467, 7376, 1123, 3820. |
 |
A Class C fire extinguisher is used on fires that involve
live electrical equipment which require the use of electrically nonconductive
extinguishing agents. (Once the electrical equipment is deenergized,
extinguishers for Class A or B fires may be used.) Extinguishers that
are suitable for Class C fires should be identified by a circle
containing the letter "C." If in color, the circle should
be blue. For Class C fire extinguisher options, please
see LSS#
8774, 5467, 7376, 1123, 3820. |
 |
A Class D fire extinguisher is used on combustible metals
such as magnesium, titanium, sodium, etc., which require an extinguishing
medium that does not react with the burning metal. Extinguishers that
are suitable for Class D fires should be identified by a five-
point painted star containing the letter "D." If in color,
the star should be yellow. For Class D fire extinguisher
options, please see LSS#
9853, 52329. |
|
|
A Class K fire extinguisher is used on fires involving
cooking media (fats, grease, and oils) in commercial cooking such
as restaurants. These fire extinguishers work on the principal of
saponification. Saponification takes place when alkaline mixtures
such as potassium acetate, potassium citrate or potassium carbonate
are applied to burning cooking oil or fat. The alkaline mixture combined
with the fatty acid create a soapy foam on the surface which holds
in the vapors and steam and extinguishes the fire. These extinguishers
are identified by the letter K. For Class
K fire extinguisher option, please see LSS #138233. |
Labeling
Fire extinguishers are labeled so users can quickly identify the classes
of fire on which the extinguisher will be effective. The marking system
combines pictographs of both recommended and unacceptable extinguisher
types on a single identification label. Following are examples of typical
labels.
| Extinguisher for Class A, B and C |
 |
 |
 |
| Extinguisher for Class B and C |
 |
 |
 |
| Extinguisher for Class A and B |
 |
 |
 |
Also located on the fire extinguisher label is the UL rating.
The UL rating is broken down into Class A and Class B:C ratings. These
numerical ratings allow you to compare the relative extinguishing effectiveness
of various fire extinguishers. For example, an extinguisher that is rated
4A:20B:C indicates the following:
- The A rating is a water equivalency rating. Each A is equivalent to
1.25 gallons of water. 4A=5 gal. of water.
- The B:C rating is equivalent to the amount of square footage that
related to the degree of training and experience of the operator, the
extinguisher can cover. 20 B:C=20 sq. ft. of coverage.
- C indicates it is suitable for use on electrically energized equipment.
When analyzing these ratings, note that there is not a numerical
rating for Class C or Class D fires. Class C fires are essentially either
a Class A or Class B fire involving energized electrical equipment where
the fire extinguishing media must be non-conductive. The fire extinguisher
for a Class C fire should be based on the amount of the Class A or Class
B component. For extinguisher use on a Class D fire, the relative effectiveness
is detailed on the extinguisher nameplate for the specific combustible
metal fire for which it is recommended.
Location
OSHA requires that employers select and distribute fire
extinguishers based on the classes of anticipated workplace fires and
also on the size and degree of the hazard which would affect their use.
The following chart contains OSHA requirements for classes of fires and
travel distance to an extinguisher. NOTE: There is no distance requirement
for Class K extinguishers. They are typically located at the point of
possible cooking fire ignition. Some local requirements may be more strict,
so you should always check with your local fire marshal and insurance
agent.
| Fire Class |
Travel Distance |
|
| Class A* |
75 ft. (22.9m) or less |
| Class B |
50 ft. (15.2m) |
| Class C |
Based on appropriate
A or B Hazard |
| Class D |
75 ft. |
*The employer may use uniformly spaced standpipe systems
or hose stations connected to a sprinkler system installed for emergency
use by employees instead of Class A portable fire extinguishers. Such
systems must meet the respective requirements of 29
CFR 1910.158 or 1910.159that
they provide total coverage of the area to be protected, and that employees
are trained at least annually in their use.
Training
Where the employee has provided fire extinguishers for employee
use, the employer shall provide an educational program to familiarize
employees on the principles and use of the extinguishers. This educational
program should be completed during the initial hiring and annualy thereafter.
*Click
here for Fire Extinguisher Training System #144030-1.
Inspections
Portable fire extinguishers must be visually inspected monthly
per 1910.157
(e)(2). The inspection should assure that:
- Fire extinguishers are in their assigned place;
- Fire extinguishers are not blocked or hidden;
- Fire extinguishers are mounted in accordance with NFPA Standard No.
10 (Portable Fire Extinguisher);
- Pressure gauges show adequate pressure (CO2 extinguisher must be weighed
to determine if leakage has occurred);
- Pin and seals are in place;
- Fire extinguishers show no visual sign of damage or abuse;
- Nozzles are free of blockage.
Maintenance of an extinguisher means a complete examination, and involves
disassembly and inspection of each part and replacement where necessary.
Maintenance should be done at least annually or more often if conditions
warrant. Hydrostatic testing of portable fire extinguishers is done to
protect against unexpected in-service failure. This can be caused by internal
corrosion, external corrosion, damage from abuse, etc. Hydrostatic testing
must be performed by trained personnel with proper test equipment and
facilities. OSHA requires hydrostatic testing according to the following
schedule:
Table 1 From 29 CFR 1910.157
| Type of Extinguisher |
Test Interval
(Years) |
|
|
| Soda acid (soldered brass shells) (until 1/1/82) |
(*) |
| Soda acid (stainless steel shell) |
5 |
| Cartridge operated water and/or antifreeze |
5 |
| Stored pressure water and/or antifreeze |
5 |
| Wetting agent |
5 |
| Foam (soldered brass shells) (until 1/1/82) |
(*) |
| Foam (stainless steel shell) |
5 |
| Aqueous Film Forming Foam (AFFF) |
5 |
| Loaded stream |
5 |
| Dry chemical with stainless steel |
5 |
| Carbon dioxide |
5 |
| Dry chemical, stored pressure, with mild steel, brazed brass or
aluminum shells |
12 |
| Dry chemical, cartridge or cylinder operated, with mild steel shells |
12 |
| Halon 1211 |
12 |
| Halon 1301 |
12 |
| Dry powder, cartridge or cylinder operated with mild steel shells |
12 |
|
|
| * Extinguishers having shells constructed of copper
or brass joined by soft solder or rivets shall not be hydrostatically
tested and shall be removed from service by January 1, 1982. (Not
permitted.) |
Maintenance, inspection and testing of an extinguisher
is the responsibility of the employer. Maintenance should be done
at least annually or more often if conditions warrant. The employer
shall record the annual maintenance date and keep these records
for one year after the recorded date or the life of the shell
of the extinguisher. For inspection tag options, please see LSS#
26498F
or 26498P.
Hydrostatic testing of portable fire extinguishers is done
to protect against unexpected in-service failure. This can be caused by
internal corrosion, external corrosion, and damage from abuse, etc. Hydrostatic
testing must be performed by trained personnel with proper test equipment
and facilities. OSHA requires hydrostatic testing according to the schedule
listed in 29 CFR 1910.157 Table L-1.
Fire extinguishers, correctly used on the type of fire they
are intended for can have a large role in stopping major fire damage and
dollar losses. When walking by a fire extinguisher, you'll know that all
of the letters and numbers have specific meanings and why it is located
where it is.
For additional information on portable fire extinguishers
and their proper placement and use, contact your local fire department.
Commonly Asked Questions
| Q. |
Are signs required to identify fire extinguisher locations? |
| A. |
Locations must be identified, but signs are not required. 29
CFR 1910.157(c)(1) |
| Q. |
Can halon still be purchased in a portable fire extinguisher? |
| A. |
Recycled halon can still be used in portable fire extinguishers,
although it is very expensive and alternatives such as CO2 should
be used when possible. Because of environmental concerns, Lab Safety
Supply no longer carriers halon fire extinguishers. |
Sources for More Information
29
CFR 1910.157, Portable Fire Extinguishers.
29
CFR 1910.158, Standpipe and Hose Systems.
29
CFR 1910.159, Automatic Sprinkler Systems.
NFPA Standard #10, Portable Fire Extinguishers.
ANSI/UL 711 Rating and Testing of Fire Extinguishers.
National Fire Protection Association, Fire Protection
Handbook, Sixteenth Edition. R.R. Donnelley & Sons.
National Safety Council, Accident Prevention Manual for
Industrial Operations, Engineering and Technology, Ninth Edition.
R.R. Donnelley & Sons.
American National
Standards Institute (ANSI)
25 West 43rd Street, 4th floor
New York, NY 10036
(212) 642-4900
National Fire Protection
Association (NFPA)
1 Batterymarch Park
P.O. Box 9101
Quincy, MA 02269
(617) 770-3000
National Safety Council
1121 Spring Lake
Itosca, IL 60143-3201
800-621-7615
Underwriters' Laboratories
(UL)
333 Pfingsten Rd.
Northbrook, IL 60062
(708) 272-8800
|
Stay on top of SAFETY in your workplace! The
LSS Online Training Center is the one-stop shop for your safety
and compliance needs. One low annual membership fee gives you a
smorgasbord of tools to manage your safety program as well as access
to economical on-line safety training! Click on the logo above for
more information. |
FREE Technical Support
When you have a question, you can rely on our team of technical experts.
They'll answer your questions about product specifications, chemical compatibility,
regulatory issues, and general worker safety and health.
Call our Safety TECHline Technical Support toll-free: 800-356-2501
(6 a.m. to 9 p.m. CT, Monday - Friday). Or e-mail our Technical Support
Staff at techsvc@labsafety.com
anytime!
FREE Catalog
For products to meet all your workplace safety and industrial needs, turn
to Lab Safety Supply. In it you'll find thousands of safety and industrial
products, plus a complete service package and our 100% guarantee to stand
behind them.
Click here to select a catalog and
fill out a request form on-line, or call today to reserve your free copy:
800-356-0783 (7 a.m. to 9 p.m. CT, Monday - Friday).
Please Note: The information contained in this
publication is intended for general information purposes only. This publication
is not a substitute for review of the applicable government regulations
and standards, and should not be construed as legal advice or opinion.
Readers with specific questions should refer to the cited regulation or
consult with an attorney.
|
|
|
|
|