A Class A fire extinguisher is used for ordinary combustibles, such as wood, paper, some plastics and textiles. This class of fire requires the heat-absorbing effects of water or the coating effects of certain dry chemicals. Extinguishers that are suitable for Class A fires should be identified by a triangle containing the letter "A." If in color, the triangle should be green. For Class A fire extinguisher options, please see LSS# 8774, 5467, 7376, 1123, 3820. |
![]() |
A Class B fire extinguisher is used for flammable liquid and gas fires such as oil, gasoline, etc. These fire extinguishers deprive the fire of oxygen and interrupt the fire chain by inhibiting the release of combustible vapors. Extinguishers that are suitable for Class B fires should be identified by a square containing the letter "B." If in color, the square should be red. For Class B fire extinguisher options, please see LSS# 8774, 5467, 7376, 1123, 3820. |
![]() |
A Class C fire extinguisher is used on fires that involve live electrical equipment which require the use of electrically nonconductive extinguishing agents. (Once the electrical equipment is deenergized, extinguishers for Class A or B fires may be used.) Extinguishers that are suitable for Class C fires should be identified by a circle containing the letter "C." If in color, the circle should be blue. For Class C fire extinguisher options, please see LSS# 8774, 5467, 7376, 1123, 3820. |
![]() |
A Class D fire extinguisher is used on combustible metals such as magnesium, titanium, sodium, etc., which require an extinguishing medium that does not react with the burning metal. Extinguishers that are suitable for Class D fires should be identified by a five- point painted star containing the letter "D." If in color, the star should be yellow. For Class D fire extinguisher options, please see LSS# 9853, 52329. |
![]() |
A Class K fire extinguisher is used on fires involving cooking media (fats, grease, and oils) in commercial cooking such as restaurants. These fire extinguishers work on the principal of saponification. Saponification takes place when alkaline mixtures such as potassium acetate, potassium citrate or potassium carbonate are applied to burning cooking oil or fat. The alkaline mixture combined with the fatty acid create a soapy foam on the surface which holds in the vapors and steam and extinguishes the fire. These extinguishers are identified by the letter K. For Class K fire extinguisher option, please see LSS #138233. |
Labeling
Fire extinguishers are labeled so users can quickly identify the classes of fire on which the extinguisher will be effective. The marking system combines pictographs of both recommended and unacceptable extinguisher types on a single identification label. Following are examples of typical labels.
| Extinguisher for Class A, B and C | ||
![]() |
![]() |
![]() |
| Extinguisher for Class B and C | ||
![]() |
![]() |
![]() |
| Extinguisher for Class A and B | ||
![]() |
![]() |
![]() |
| Extinguisher for Class A | ||
![]() |
![]() |
![]() |
Also located on the fire extinguisher label is the UL rating. The UL rating is broken down into Class A and Class B:C ratings. These numerical ratings allow you to compare the relative extinguishing effectiveness of various fire extinguishers. For example, an extinguisher that is rated 4A:20B:C indicates the following:
When analyzing these ratings, note that there is not a numerical rating for Class C or Class D fires. Class C fires are essentially either a Class A or Class B fire involving energized electrical equipment where the fire extinguishing media must be non-conductive. The fire extinguisher for a Class C fire should be based on the amount of the Class A or Class B component. For extinguisher use on a Class D fire, the relative effectiveness is detailed on the extinguisher nameplate for the specific combustible metal fire for which it is recommended.
Location
OSHA requires that employers select and distribute fire extinguishers based on the classes of anticipated workplace fires and also on the size and degree of the hazard which would affect their use. The following chart contains OSHA requirements for classes of fires and travel distance to an extinguisher. NOTE: There is no distance requirement for Class K extinguishers. They are typically located at the point of possible cooking fire ignition. Some local requirements may be more strict, so you should always check with your local fire marshal and insurance agent.
| Fire Class | Travel Distance |
| |
|
| Class A* | 75 ft. (22.9m) or less |
| Class B | 50 ft. (15.2m) |
| Class C | Based on appropriate A or B Hazard |
| Class D | 75 ft. |
*The employer may use uniformly spaced standpipe systems or hose stations connected to a sprinkler system installed for emergency use by employees instead of Class A portable fire extinguishers. Such systems must meet the respective requirements of 29 CFR 1910.158 or 1910.159that they provide total coverage of the area to be protected, and that employees are trained at least annually in their use.
Training
Where the employee has provided fire extinguishers for employee use, the employer shall provide an educational program to familiarize employees on the principles and use of the extinguishers. This educational program should be completed during the initial hiring and annualy thereafter.
*Click here for Fire Extinguisher Training System #144030-1.
Inspections
Portable fire extinguishers must be visually inspected monthly per 1910.157 (e)(2). The inspection should assure that:
The maintenance requirements are dependent on the type of portable fire extinguisher. Stored pressure (or dry chemical type) extinguishers do not require an internal examination. Water or steam type fire extinguishers should be discharged, disassembled, and inspected annually (NFPA 10, 4-4.1.1). Dry chemical extinguishers that require a 12-year hydrostatic test are required to be emptied and subjected to applicable maintenance procedures every 6 years. Non-refillable, disposable dry chemical extinguishers are exempt from this requirement (29 CFR 1910.157(e)(4)). For additional fire extinguisher maintenance, follow the manufacturer's suggested maintenance procedure as presented in the operating manual. Hydrostatic testing of portable fire extinguishers is done to protect against unexpected in-service failure. This can be caused by internal corrosion, external corrosion, damage from abuse, etc.
Hydrostatic testing must be performed by trained personnel with proper test equipment and facilities. OSHA requires hydrostatic testing according to the following schedule:
Table 1 From 29 CFR 1910.157
| Type of Extinguisher | Test Interval (Years) |
| Soda acid (soldered brass shells) (until 1/1/82) | (*) |
| Soda acid (stainless steel shell) | 5 |
| Cartridge operated water and/or antifreeze | 5 |
| Stored pressure water and/or antifreeze | 5 |
| Wetting agent | 5 |
| Foam (soldered brass shells) (until 1/1/82) | (*) |
| Foam (stainless steel shell) | 5 |
| Aqueous Film Forming Foam (AFFF) | 5 |
| Loaded stream | 5 |
| Dry chemical with stainless steel | 5 |
| Carbon dioxide | 5 |
| Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shells | 12 |
| Dry chemical, cartridge or cylinder operated, with mild steel shells | 12 |
| Halon 1211 | 12 |
| Halon 1301 | 12 |
| Dry powder, cartridge or cylinder operated with mild steel shells | 12 |
| * Extinguishers having shells constructed of copper or brass joined by soft solder or rivets shall not be hydrostatically tested and shall be removed from service by January 1, 1982. (Not permitted.) | |
Maintenance, inspection and testing of an extinguisher is the responsibility of the employer. Maintenance should be done at least annually or more often if conditions warrant. The employer shall record the annual maintenance date and keep these records for one year after the recorded date or the life of the shell of the extinguisher. For inspection tag options, please see LSS# 26498F or 26498P.
Hydrostatic testing of portable fire extinguishers is done to protect against unexpected in-service failure. This can be caused by internal corrosion, external corrosion, and damage from abuse, etc. Hydrostatic testing must be performed by trained personnel with proper test equipment and facilities. OSHA requires hydrostatic testing according to the schedule listed in 29 CFR 1910.157 Table L-1.
Fire extinguishers, correctly used on the type of fire they are intended for can have a large role in stopping major fire damage and dollar losses. When walking by a fire extinguisher, you'll know that all of the letters and numbers have specific meanings and why it is located where it is.
For additional information on portable fire extinguishers and their proper placement and use, contact your local fire department.
Commonly Asked Questions
| Q. | Are signs required to identify fire extinguisher locations? |
| A. | Locations must be identified, but signs are not required. 29 CFR 1910.157(c)(1) |
| Q. | Can halon still be purchased in a portable fire extinguisher? |
| A. | Recycled halon can still be used in portable fire extinguishers, although it is very expensive and alternatives such as CO2 should be used when possible. Because of environmental concerns, Lab Safety Supply no longer carriers halon fire extinguishers. |
Sources for More Information
29 CFR 1910.157, Portable Fire Extinguishers.
29 CFR 1910.158, Standpipe and Hose Systems.
29 CFR 1910.159, Automatic Sprinkler Systems.
NFPA Standard #10, Portable Fire Extinguishers.
ANSI/UL 711 Rating and Testing of Fire Extinguishers.
National Fire Protection Association, Fire Protection Handbook, Sixteenth Edition. R.R. Donnelley & Sons.
National Safety Council, Accident Prevention Manual for Industrial Operations, Engineering and Technology, Ninth Edition. R.R. Donnelley & Sons.
American
National Standards Institute (ANSI)
25 West 43rd Street, 4th floor
New York, NY 10036
(212) 642-4900
National
Fire Protection Association (NFPA)
1 Batterymarch Park
P.O. Box 9101
Quincy, MA 02269
(617) 770-3000
National
Safety Council
1121 Spring Lake
Itosca, IL 60143-3201
800-621-7615
Underwriters'
Laboratories (UL)
333 Pfingsten Rd.
Northbrook, IL 60062
(708) 272-8800
Stay on top of SAFETY in your workplace! The
LSS Online Training Center is the one-stop shop for your safety
and compliance needs. One low annual membership fee gives you a
smorgasbord of tools to manage your safety program as well as access
to economical on-line safety training! Click on the logo above for
more information. |
FREE Technical Support
When you have a question, you can rely on our team of technical experts.
They'll answer your questions about product specifications, chemical compatibility,
regulatory issues, and general worker safety and health.
Call our Safety TECHline Technical Support toll-free: 800-356-2501
(6 a.m. to 9 p.m. CT, Monday - Friday). Or e-mail our Technical Support
Staff at techsvc@labsafety.com
anytime!
FREE Catalog
For products to meet all your workplace safety and industrial needs, turn
to Lab Safety Supply. In it you'll find thousands of safety and industrial
products, plus a complete service package and our 100% guarantee to stand
behind them.
Click here to select a catalog and
fill out a request form on-line, or call today to reserve your free copy:
800-356-0783 (7 a.m. to 9 p.m. CT, Monday - Friday).
Please Note: The information contained in this publication is intended for general information purposes only. This publication is not a substitute for review of the applicable government regulations and standards, and should not be construed as legal advice or opinion. Readers with specific questions should refer to the cited regulation or consult with an attorney.
| EZ Facts Sections | ||